QuickZone

QuickZone

High-performance conventional fire panel and twin-wire fire panel range
Overview

QuickZone is our fuss-free conventional fire panel range.

Quick to fit, configure and maintain, QuickZone delivers performance, quality and ease of use in a flexible, conventional format capable of covering 2 to 32 zones.

Available in standard and XL formats, QuickZone is approved to EN54 Parts 2 and 4 and delivers a host of performance, configuration and programming benefits.

BIM objects for QuickZone are available are on NBS Source.

Product Features

  • Compatible with leading conventional detectors, QuickZone has many time-saving benefits
  • Generous wiring space and multiple knockouts make it quick to install
  • Other fuss-free features include easy-change PCBs, simple access to batteries, a no-crimp metal earth bar, three power switch modes and no need for end-of-line modules
  • Zone interface function allows last zone to be set via DIL for non-latching operation
  • Up to 32 fire zones
  • DIL switch selection of twin-wire/conventional format*
  • 2 open collector outputs
  • 2 volt-free contacts
  • 28V output
  • Zone interface function allows last zone to be set via DIL for non-latching operation
  • 2 inputs (class change and alert)
  • Up to 6 sounder circuits
  • Spare zones can be used as sounder circuits
  • Common fire output and relay can be programmed to cancel on silence
  • Modular expansion zone cards available
  • XL system includes repeater panel

*DIL switch selection of twin-wire not available with QuickZone XL 16-32 zone fire panel.

  • Simple, clear LED indication of fire, system status and zone status
  • One-button fault diagnosis
  • Colour-coded keypad to manage re-sound, silence, reset, test, disable, mute and test lamps
  • Simple 3-level programming accessible by keyswitch or keycode and DIL
  • Disablements removed with one code
  • Factory reset option
  • 3-button action to disable zones
  • Buzzer mute in fault condition
  • In test mode, tests can be run with or without sounders
  • False alarm management
  • 40 event log (XL only)
  • Full technical support
  • 3-year warranty

To maximise configuration options, QuickZone allows individual zones to have specific programmed options including:

  • Set as latching or non-latching
  • Short circuit = Fire for monitoring
  • Specified for MTL5061 I.S barrier compatibility
  • Compatible with schottky or zener diode bases
  • False alarm management modes
  • Set delays to outputs
  • Silent mode for indication purposes – visual and audible alarm at panel but no sounder operation
  • Detector removal monitoring can be turned off for older non-approved detectors (non-compliant to EN54.)
  • Twin wire zone can be programmed to zone of origin continuous ringing. Other zones can be set to pulsing, silence or continuous.
  • Two independent programmable inputs – class change and alert input
  • Either or both inputs can be programmed for remote evacuation, remote silence alarm, remote reset.
  • Inputs programmable for indication purposes so the zone 12 LED or fault LED will illuminate.
  • Two additional programmable inputs (remote reset & remote silence alarms), are available on the 16-32 zone panels.
  • Can be set to latching
  • Fault outputs can be inverted
  • Aux relays and all outputs, including sounders, are independently programmable:
    • On, off or pulsing
    • Programmed to a dedicated zone
    • Programmed with a custom response to silence alarm, evacuate, class change input, alert input or during zone delay.
  • Other sounders can be switched off, pulsing or continuous
  • Output delays can be applied to aux outputs and sounders (for example investigation delay for false alarm management).

QuickZone false alarm management compliance with EN54-2

QuickZone false alarm management functions according to one of three different modes as described in EN54-2.

QuickZone supports mode A while Quickzone XL supports all three modes.

False alarm management can be selected for individual zones on both panels.

Mode A

The first alarm is not indicated and the sounders do not activate. The panel resets and rechecks the zone within 15-30 seconds, if an alarm is detected the panel activates a full fire condition. Any new alarm from the same or a different zone within 30 minutes also activates a full fire condition.

Mode B

The first alarm will indicate at the panel but the sounders do not activate. The panel resets and rechecks the zone within a programmable time period (1 – 4 minutes). If an alarm is detected the panel activates a full fire condition. Any new alarm from the same or a different zone within a second programmable time period of 5 to 30 minutes will also activate a full fire condition unless the reset button is pressed.

Mode C

The first alarm will indicate at the panel but the sounders do not activate. The panel will not activate a full fire condition unless a second device is activated in the same or a different zone.

 

Want to Know More?

If you’d like advice about protecting your critical site from fire, we have a wealth of experience to share. Simply get in touch using the form below…

We collect personal information when you provide your details to us. We only use the data collected through this form to update you on your query. We will not share your information for marketing purposes with companies outside of our business. To find out more about how we store and use your information, please read our Privacy Policy
Subscribe to our newsletter
We collect personal information when you provide your details to us. We only use the data collected through this form to update you on job updates at Nissan. We will not share your information for marketing purposes with companies outside of our business. To find out more about how we store and use your information, please read our Privacy Policy